Voltage limits (peak value)
The following voltage limits can be changed:
n
Upper disconnection value
1)
n
Lower disconnection value
1)
(Fig. left)
1)
The disconnection value relates to the peak value of the voltage.
Frequency limits
The following frequency limits can be changed:
n
Upper disconnection value
n
Lower disconnection value (Fig. left)
n
Derating switch-on threshold (because frequency is too high)
n
Frequency threshold when switching on again
Voltage limits ø (average value)
The following voltage limits can be changed:
n
Upper disconnection value
1)
(Fig. left)
n
Lower disconnection value
1)
1)
The disconnection value relates to the average value of the
voltage.
Reactive power characteristic curve
Overview
The reactive power characteristic curve must be set during initial
commissioning if this is prescribed for the previously selected
country. The following applies:
n
3 characteristic curves are available for selection (Fig. left):
–
Default. char. curve
(pre-defined)
–
Enter char. curve
(manually adjustable)
–
Char. curve cos φ = 1
(pre-defined)
n
After configuration, the characteristic curve is displayed as a
graph (example in Fig. left).
①
x-axis, output power P in %
②
y-axis, phase shift cos
φ
③
Nodes (in example: 4 nodes)
④
Arrow symbol
Overexcitation
⑤
Arrow symbol
Underexcitation
GB
747.431 | Z08 | 2014-01-31
95
Содержание coolcept StecaGrid 1800
Страница 76: ...DE 747 431 Z08 2014 01 31 76...
Страница 121: ...Entering system data 1 2 3 4 5 6 7 7 8 9 10 11 Fig 12 Data entry form for the system data GB 747 431 Z08 2014 01 31 121...
Страница 146: ...GB 747 431 Z08 2014 01 31 146...
Страница 147: ...1 Montage Installation Montage 148 2 Zertifikate Certificates Certificats 162 747 431 Z08 2013 12 10 147...
Страница 149: ...coolcept x 150 mm 240 mm 45 mm 210 mm 190 mm 320 mm 400 mm 748 339 Z01 747 431 Z08 2013 12 10 149...
Страница 162: ...2 Zertifikate Certificates Certificats 747 431 Z08 2013 12 10 162...
Страница 163: ...747 431 Z08 2013 12 10 163...
Страница 164: ...747431...