4. Press
s
. The next value is selected.
5. Repeat steps 1 to 4 for the remaining values.
6. Press
ESC
. The next higher menu level is displayed.
Calling up the service menu and editing the values
ATTENTION!
Risk of yield losses and contravention of regulations and standards. Inverter and grid parameters
can be changed in the service menu. The service menu must therefore only be used by technical
professionals who know the applicable regulations and standards.
1. Select the
Service
menu item.
2. Press
SET
. The fig. shown at the left appears.
3. Press
rs
simultaneously for 3 seconds. The service menu is
displayed (Fig. left).
4. Press
rs
to select a menu item.
5. Press
SET
to edit the menu item. The following applies:
n
Enter the password if required (Fig. left); see
n
If necessary, press
rs
within a menu item to display and
edit other settings (e.g.
Voltage limits
).
n
The menu items are described in
5.4 Internet portal
Notice
–
The Internet portal only supports inverters in the coolcept product line.
–
The following illustrations show examples in English.
GB
747.431 | Z08 | 2014-01-31
118
Содержание coolcept StecaGrid 1800
Страница 76: ...DE 747 431 Z08 2014 01 31 76...
Страница 121: ...Entering system data 1 2 3 4 5 6 7 7 8 9 10 11 Fig 12 Data entry form for the system data GB 747 431 Z08 2014 01 31 121...
Страница 146: ...GB 747 431 Z08 2014 01 31 146...
Страница 147: ...1 Montage Installation Montage 148 2 Zertifikate Certificates Certificats 162 747 431 Z08 2013 12 10 147...
Страница 149: ...coolcept x 150 mm 240 mm 45 mm 210 mm 190 mm 320 mm 400 mm 748 339 Z01 747 431 Z08 2013 12 10 149...
Страница 162: ...2 Zertifikate Certificates Certificats 747 431 Z08 2013 12 10 162...
Страница 163: ...747 431 Z08 2013 12 10 163...
Страница 164: ...747431...