4.9 De-installing the inverter
DANGER!
Risk of death by electrocution! Only technical professionals may perform the work described in this
section. Follow the safety instructions at the beginning of the Section "Installation".
Switching off the AC and DC supplies
1. Turn the AC circuit breaker to off.
2. Set the DC circuit breaker on the inverter to position
0
(Fig.
left).
Disconnecting the DC connections from the inverter
u
Disconnect the DC cable plug connectors according to the
manufacturer's instructions; see Appendix. A special tool is
required for Multi-Contact MC4.
—————————————————————————
Warning
DC cables carry voltage when the solar modules are subjected to
sunlight.
—————————————————————————
Disconnecting the AC plug from the inverter
1. Remove the AC plug from the socket on the inverter as
described in the Appendix under Mounting
⇒
AC plugs.
2. Check that all pins of the AC plug are free of voltage. Use a
suitable voltmeter for this (do not use a simple neon phase
checker).
Opening the AC plug (only if required)
u
Open the AC plug as described in the Appendix under
Mounting
⇒
AC plugs.
GB
747.431 | Z08 | 2014-01-31
113
Содержание coolcept StecaGrid 1800
Страница 76: ...DE 747 431 Z08 2014 01 31 76...
Страница 121: ...Entering system data 1 2 3 4 5 6 7 7 8 9 10 11 Fig 12 Data entry form for the system data GB 747 431 Z08 2014 01 31 121...
Страница 146: ...GB 747 431 Z08 2014 01 31 146...
Страница 147: ...1 Montage Installation Montage 148 2 Zertifikate Certificates Certificats 162 747 431 Z08 2013 12 10 147...
Страница 149: ...coolcept x 150 mm 240 mm 45 mm 210 mm 190 mm 320 mm 400 mm 748 339 Z01 747 431 Z08 2013 12 10 149...
Страница 162: ...2 Zertifikate Certificates Certificats 747 431 Z08 2013 12 10 162...
Страница 163: ...747 431 Z08 2013 12 10 163...
Страница 164: ...747431...