The wiring diagram of the RS485 bus is shown below.
1
2
3
4
5
5
5
RS485
RS485
RS485
Fig. 5: Wiring diagram
①
External data logger
②
First inverter
③
Inverter
④
Last inverter, terminated
⑤
Standard RJ45 cable (patch cable)
3.6.4 Alternative data connection cable
ATTENTION!
Material damage caused by electrical voltage! The alternative data connection cable may only be
manufactured by professional personnel.
The alternative data connection cable is a Cat-5 cable for long data connections. The following
applies to the alternative data connection cable:
n
The total length of the RS485 bus must not exceed 1,000 m (Master/first inverter to last
inverter).
n
Use the pin assignment according to the table below if the alternative data connection cable is
connected to the RJ45 socket of the first inverter or to the connector of an external data logger.
Pin assignments of the alternative data cable
Device
Inverter
Solar-Log
WEB‘log
1)
Signal
¤
Connection
RJ45
Terminal strip
RJ12
Pin
1
1
2
Data A
2
4
4
Data B
3
—
—
—
4
—
—
—
GB
747.431 | Z08 | 2014-01-31
100
Содержание coolcept StecaGrid 1800
Страница 76: ...DE 747 431 Z08 2014 01 31 76...
Страница 121: ...Entering system data 1 2 3 4 5 6 7 7 8 9 10 11 Fig 12 Data entry form for the system data GB 747 431 Z08 2014 01 31 121...
Страница 146: ...GB 747 431 Z08 2014 01 31 146...
Страница 147: ...1 Montage Installation Montage 148 2 Zertifikate Certificates Certificats 162 747 431 Z08 2013 12 10 147...
Страница 149: ...coolcept x 150 mm 240 mm 45 mm 210 mm 190 mm 320 mm 400 mm 748 339 Z01 747 431 Z08 2013 12 10 149...
Страница 162: ...2 Zertifikate Certificates Certificats 747 431 Z08 2013 12 10 162...
Страница 163: ...747 431 Z08 2013 12 10 163...
Страница 164: ...747431...