STATUS SCIENTIFIC CONTROLS
Installation, Commissioning & Routine Gas Testing
FGD10A-M Gas Detector
TD18/032
Issue:
10
Change Note:
1869
Page 46
9.1.12.4 Display LEL and CF
This is selectable via Diagnostics 2 screen and applies to IR flammable sensors only.
Diagnostics 2
Exit
Select:
Display LEL and CF
Test Relays
Cycling pages of all the IR flammable gases with correction factor and Lel is displayed
via a table e.g.:
Page 1 only is shown here:
Diagnostics 2
Menu= Exit
GAS CF Lel
Methane ---- 5.0
Propane ---- 2.0
Butane 0.97 1.6
Chloromethane 4.97 8.1
Cyclopentane 1.62 1.1
9.1.12.5 Test Relays
Each relay may be selected in turn for testing. Press ENTER to
momentarily activate the Relay.
Test Relays
Menu= Exit
Relay:
1 2 3