STATUS SCIENTIFIC CONTROLS
Installation, Commissioning & Routine Gas Testing
FGD10A-M Gas Detector
TD18/032
Issue:
10
Change Note:
1869
Page 72
LOGICAL
ADDRESS
(R/W)
DATA
TYPE
DESCRIPTION
40306
R
uINT16
Alarm1 Seconds
The second the most recent alarm1
occurred e.g. 0x002F= 47
40307
R
uINT16
Alarm2 Year
The year the most recent alarm1
occurred e.g. 0x000D= 2013
40308
R
uINT16
Alarm2 Month
The month the most recent alarm1
occurred e.g. 0x0006= June
40309
R
uINT16
Alarm2 Day
The day the most recent alarm2
occurred e.g. 0x0013 =19th
40310
R
uINT16
Alarm2 Hours
The hour the most recent alarm2
occurred e.g. 0x000D =1 pm
40311
R
uINT16
Alarm2 Minutes
The minute the most recent alarm2
occurred e.g. 0x001C= 28
Note: When Alarm level values are changed, the corresponding
time/date event register is set to zero.
LOGICAL
ADDRESS
(R/W)
DATA
TYPE
DESCRIPTION
40312
R
uINT16
Alarm2 Seconds
The second the most recent alarm2
occurred e.g. 0x002F= 47
40313
R
uINT16
Alarm3 Year
Not implemented. Returns 0.
40314
R
uINT16
Alarm3 Month
Not implemented. Returns 0.
40315
R
uINT16
Alarm3 Day
Not implemented. Returns 0.
40316
R
uINT16
Alarm3 Hours
Not implemented. Returns 0.
40317
R
uINT16
Alarm3 Minutes
Not implemented. Returns 0.
40318
R
uINT16
Alarm3 Seconds
Not implemented. Returns 0.