STATUS SCIENTIFIC CONTROLS
Installation, Commissioning & Routine Gas Testing
FGD10A-M Gas Detector
TD18/032
Issue:
10
Change Note:
1869
Page 47
9.1.12.6 Modbus Data
This is useful for diagnosing the Modbus communications problems by displaying
some bus data in real time. The displayed parameters are as follows
for received
data only by the FGD10AM from the Modbus master controller.
All values in are
in hex:
Diagnostics 1
Exit
Slaveaddr:
01
03
Command:
Register:
ChecksumL:
ChecksumH:
0064
d5
c5
Slaveaddr: Modbus node address of target FGD10AM e.g. 01
Command: Modbus command e.g.
03 “Read holding register”
Register: Target register to read e.g. 64H =100d
ChecksumH: High order byte of CRC for incoming message
ChecksumL: Low order byte of CRC for incoming message