STATUS SCIENTIFIC CONTROLS
Installation, Commissioning & Routine Gas Testing
FGD10A-M Gas Detector
TD18/032
Issue:
10
Change Note:
1869
Page 32
•
Press Menu
to exit
55
Flammable
22/05/2013
15:33:26
%LEL
Propane
9.1.4. Sensor FSD
.
Sensor FSD
Edit
100
The sensor measuring range is set by this menu.
•
Use the
button to select an individual digit then use the
button to change the digit to 0 through 9, continue for all digits
until the desired FSD is set.
.
•
Press ENTER to accept the new gas level will be
displayed to confirm the new FSD.
Note: Pressing MENU instead of ENTER will exit the menu without changing
the value.
Press MENU to close the menu system.
Note: changing the FSD must be used with caution. The setting must be
within the capability of the sensor.
Updated