STATUS SCIENTIFIC CONTROLS
Installation, Commissioning & Routine Gas Testing
FGD10A-M Gas Detector
TD18/032
Issue:
10
Change Note:
1869
Page 68
LOGICAL
ADDRESS
(R/W)
DATA
TYPE
DESCRIPTION
40115
R
uINT16
Last Alarm date
(mmdd)
MSB=month (0x01 to 0x0C)
LSB=day (0x01 to 0x1F)
returns zero if no alarm has ever
occurred.
40115
R
uINT16
Last Alarm date
(mmdd)
MSB=month (0x01 to 0x0C)
LSB=day (0x01 to 0x1F)
Returns zero if no alarm has ever
occurred.
40116
R
uINT16
Last Alarm date
(00yy)
LSB=0
MSB=year e.g. 0x0D for 2013.
40117
R/W
uINT16
RTC
(mmdd)
MSB=month (0x01 to 0x0C)
LSB=day (0x01 to 0x1F)
40118
R/W
uINT16
RTC
(00yy)
LSB=0
MSB=year e.g. 0x0D for 2013.
40119
R/W
uINT16
RTC (hhmm)
MSB = hour e.g. 0x0A for 10am
LSB = minutes e.g. 0x3B for 59 mins.
40124
R/W
INT16
ALARM1 Level x10 see 40022
40125
R/W
INT16
ALARM2 Level x10 see 40023
40126
R/W
INT16
Gas Calibration Level see 40011
40152
W
uINT16
SPAN SENSOR
Write any value to this register to span
the sensor according to the Gas
Calibration Level
40154
W
uINT16
ZERO SENSOR
write any value to this
register to zero the sensor.
40203
R
MSFP16
Sensor temperature Float:
Most significant 16 bits of IEEE574
floating point value.
40204
R
LSFP16
Sensor temperature Float
Least significant 16 bits of IEEE574
floating point value.
40211
R/W
MSFP16
Gas Calibration Value Float
Most significant 16 bits of IEEE574
floating point value.
40212
R/W
LSFP16
Gas Calibration Value Float
Least significant 16 bits of IEEE574
floating point value.