STATUS SCIENTIFIC CONTROLS
Installation, Commissioning & Routine Gas Testing
FGD10A-M Gas Detector
TD18/032
Issue:
10
Change Note:
1869
Page 56
9.1.19. Sensor Bias (Toxic sensor only)
SET BIAS
Edit
Bias=0mv
Use the buttons select the desired bias.
This option sets the bias voltage to match the sensor fitted. Available options
are: no bias, 250 mV and 300 mV bias
The normal level is 0, no bias.
9.1.20. Gain Setting (Toxic Sensor only)
Gain Setting
Exit
POT VAL:
5
28
READING:
Allows adjustment of the electronic gain potentiometer of the Toxic sensor
electronics.
Use the keys to change the potentiometer setting.
•
Press ENTER to accept the new setting, will be
displayed
The sensor reading is also displayed in real time.
This is normally only done by SSCL personnel.
Updated