STATUS SCIENTIFIC CONTROLS
Installation, Commissioning & Routine Gas Testing
FGD10A-M Gas Detector
TD18/032
Issue:
10
Change Note:
1869
Page 66
LOGICAL
ADDRESS
(R/W)
DATA
TYPE
DESCRIPTION
40003
R
uINT16
TEMPERATURE
of sensor (IR only) in Kelvin(e.g. 303)
40009
R
uINT16
Sensor
“Restore” Type:
1=IR
2=Pellistor
3=Oxygen
4=Tox1
5= Tox2
6= Tox3
7=Tox4
8=Tox5
9= Tox6
10=Tox7
11=Tox8
40011
R/W
uINT16
Calibration Gas Level
e.g. (50 % LEL)
40022
R/W
INT16
ALARM1 LEVELx10
e.g. 0x0064 =100=10%LEL
40023
R/W
INT16
ALARM2 LEVELx10
e.g.
0x00c8=200=20%LEL
40027
R/W
uINT16
FSD range
(e.g. 0x0014=100%)
40101
R
uINT16
Sensor Type
:
LSB holds instrument Modbus address
MSB holds:
0x04 for TOX
0x05 for Oxygen
0x07 Pellistor/Catalytic
0x13 for NDIR sensor.
40102
R
INT16
GAS READING
identical to 40001
40103
R
uINT16
GAS TYPE and Decimal Places.
Ammonia = 0x0d
Butane = 0x16 “Flammable”
Carbon Monoxide = 0x01
Carbon Dioxide = 0x20
Chlorine = 0x05
Ethane = 0x16
“Flammable”
Ethanol = 0x16
“Flammable””
Ethylene Oxide = 0x36
“Flammable”
Flammable = 0x16
“Flammable”
Hexane = 0x16
“Flammable”
Hydrogen = 0x09
Hydrogen Chloride = 0x0e
Hydrogen Cyanide = 0x07
Hydrogen Fluoride = 0x21
Hydrogen Sulphide = 0x02
Methane = 0x15
Methanol = 0x16
“Flammable”
Nitric Oxide = 0x0c
Nitrous Oxide = 0x22
Oxygen = 0x14