STATUS SCIENTIFIC CONTROLS
Installation, Commissioning & Routine Gas Testing
FGD10A-M Gas Detector
TD18/032
Issue:
10
Change Note:
1869
Page 37
Updated
9.1.9.
Latching
Relays
The user can select if the relays are latched or non-latched. If the relays are
latched then they can only be cleared when the alarm condition no longer
exists and the ENTER button has been pressed during the normal screen.
•
From the menu system select menu option:
Latching
Relay
Modes
and press ENTER. The following display is shown:
Latching Relays
Edit
Off
•
Use the
button to select On and the
button to select Off.
•
Press ENTER to accept the new setting,
will be
displayed
Note: Pressing MENU instead of ENTER leaves the latching
relay setting unchanged.
•
Press the MENU button to exit the Latching Relays options. On
exit the display will show
if no changes have been
made or
if changes have been made.
Data updated
No change