STATUS SCIENTIFIC CONTROLS
Installation, Commissioning & Routine Gas Testing
FGD10A-M Gas Detector
TD18/032
Issue:
10
Change Note:
1869
Page 41
9.1.12. Diagnostics
This feature is a view-only feature. No configuration changes are possible
from within this menu.
•
From the menu system select menu option:
Diagnostics
and
press ENTER.
•
The options displayed are as follows:
Diagnostics 1
Exit
Select:
LiveData
ConfigData
CommsData
ModbusData
•
Press MENU to close the menu system.
•
Select the desired option via the UP/DOWN keys and press
ENTER
9.1.12.1 LiveData:
Consists of Several pages of data for IR sensors. Each page is displayed
automatically for several seconds. The displayed values are as follows:
Screen1 (IR):
Diagnostics 1
Exit
Reading:
Temperature:
Det1:
Ref:
Fa1:
0.0
34.6
2792
1137
0.002
0
Reading is the computed gas reading.
Temperature is the sensor temperature in °C.
Det1 is the AtoD counts for the detector1 signal.
Ref is the AtoD counts for the reference signal.
Fa1 is the computed fractional absorbance for Pyro 1.
Screen2 (IR):