STATUS SCIENTIFIC CONTROLS
Installation, Commissioning & Routine Gas Testing
FGD10A-M Gas Detector
TD18/032
Issue:
10
Change Note:
1869
Page 75
40102 in the Modbus register map. In other words Logical address 40001 in
the Modbus memory map equates to holding register physical address 0.
D0 is the PLC register assigned to hold the gas level reading = 50 (%LEL)
The ADPRW command automatically takes care of CRC generation and
checking.
In terms of a conventional Modbus packet sent to the FGD10AM this would
look like:
Slave
address
Function
command
Target
Register
Number of
registers
CRC checksum
0x01
0x03
0x00
0x65
0x00
0x01
0x94
0x15