The derating of the permissible rated current for installation altitudes of
over 1000 m and at ambient temperatures below 40 °C is calculated as
follows:
Total derating = Derating
altitude
x Derating
ambient temperature
K = K
1
x K
2
It must be borne in mind that total derating must
not be greater
than 1!
Example:
Altitude: 3000 m
K
1
= 0.845
Ambient temperature: 35 °C
K
2
= 1.125
→
Total derating = 0.845 x 1.125 = 0.95