05.2006
Parameterizing Steps
Siemens AG
6SE7087-2JD60
SIMOVERT MASTERDRIVES
Operating Instructions
9-39
9.2.3
Parameterizing by loading parameter files (download P060 = 6)
When parameterizing with download, the parameter values stored in a
master unit are transferred to the unit to be parameterized via a serial
interface. The following can serve as master units:
1. OP1S operator control panel
2. PCs with DriveMonitor service program
3. Automation units (e.g. SIMATIC)
The interface SCom1 or SCom2 with USS protocol of the basic unit and
field bus interfaces used for parameter transfer (e.g. CBP for
PROFIBUS DP) can serve as serial interfaces.
Using download, all changeable parameters can be set to new values.
Automation unit
(e. g. SIMATIC S7)
Laptop
USS-Bus
Jog
7
8
9
P
Reset
+/-
0
4
5
6
1
2
3
O
I
Fault
Run
OP1S
Operating mode
Individual operation
Bus operation
Type of construction
Compact, chassis
Compact, chassis
Terminal
X300
(SCom1)
X101
Operating mode
Individual operation
Type of construction
Compact, chassis
Terminal
X300
(SCom1)
US
S v
ia R
S4
85
USS via RS232
Operating mode
Bus operation
Type of construction
Optional board CBx
e. g. CBP for Profibus
Terminal
e. g. X448
for CBP
bu
s-s
pe
cif
ic
SIEMENS
X300
Fig. 9-4
Parameter transfer from various sources by download
Download