Control Word and Status Word
05.2006
6SE7087-2JD60 Siemens
AG
10-6
Operating Instructions
SIMOVERT MASTERDRIVES
Bit 16: Function data set FDS bit 0 command
♦
In conjunction with bit 17 "FDS BIT 1" one of the four possible
function data sets is energized.
Bit 17: Function data set FDS bit 1 command
♦
In conjunction with bit 16 "FDS BIT 0" one of the four possible
function data sets is energized.
Bit 18: Motor data set, MDS bit 0 command
READY TO POWER-UP (009), PRE-CHARGING (010) or READY
(011)
♦
One of the four possible motor data sets is energized in conjunction
with bit 19 "MDS BIT 1".
Bit 19: Motor data set, MDS bit 1 command
READY TO POWER-UP (009), PRE-CHARGING (010) or READY
(011)
♦
One of the four possible motor data sets is energized in conjunction
with bit 18 "MDS BIT 0".
Bit 20: Fixed setpoint FSW bit 0 (LSB) command
♦
In conjunction with bit 21 "FSW BIT 1", one of the four possible fixed
setpoints is energized to input as percentage fixed setpoints,
referred to the reference frequency P352 or reference speed P353.
Bit 21: Fixed setpoint FSW bit 1 (MSB) command
♦
In conjunction with bit 20 "FSW BIT 0" one of the four possible fixed
setpoints is energized for input as percentage fixed setpoints,
referred to the reference frequency P352 or the reference speed
P353.
Bit 22: Synchronizing enable command (H "synchronizing enable")
♦
For converter sychronization (P534 = 1):
HIGH signal, TSY (option) available and P100 = 2 (V/f
characteristic for textile applications).
♦
For line synchronization (P534 = 2):
HIGH signal, TSY (option) P100 = 1, 2 or 3
♦
The command enables the synchronizing function.
Result
Result
Condition
Result
Condition
Result
Result
Result
Condition
Result