Parameterizing Steps
05.2006
6SE7087-2JD60 Siemens
AG
9-26
Operating Instructions
SIMOVERT MASTERDRIVES
8
7
6
5
4
3
2
1
Setpoint source
M
A
STERDRIVES VC
OP1S and fixed setpoints (P368=7)
- s71 -
KK0046
KK0045
KK0047
KK0048
KK0040
Act.FSetp
Active FSetp
r4
2
0
P443.B (
40)
KK
Sr
c M
a
in
Setpoi
nt
P486.B (
40)
KK
Src T se
tpo
in
t
0 1 0 0
0 1 0 1
0 1 1 0
0 1 1 1
FSetp
Bit 3
P418.B
FSetp
Bit 2
P417.B
0 0 0 0
0 0 0 1
0 0 1 0
0 0 1 1
KK0042
KK0041
KK0043
KK0044
(f
o
r T co
n
tro
l)
F
ix
e
d s
e
tpoi
nt1
P401.F
F
ix
e
d s
e
tpoi
nt2
P402.F
F
ix
e
d s
e
tpoi
nt3
P403.F
F
ix
e
d s
e
tpoi
nt4
P404.F
F
ix
e
d s
e
tpoi
nt5
P405.F
F
ix
e
d s
e
tpoi
nt6
P406.F
F
ix
e
d s
e
tpoi
nt7
P407.F
F
ix
e
d s
e
tpoi
nt8
P408.F
in
%
in
Hz
Fixed
setpoints
Sheet [290]
Terminal strip
Sheet [90]
If us
ed as
di
gi
tal
i
nputs
, the par
am
eter
s
P651.B, P652.B, P653.B and P654.B m
u
st
be set to 0!
If used as digital outputs, B10 to B14 m
u
st
not be w
ir
ed.
*
)
from sheet [200]
to sheet [180]
to sheet[316.1]
to sheet[320.1]
N
M
n959.89 = 4
If P366 = 2
P590 = B0012
P651 = B0000
P652 = B0000
P653 = B0107
/5
/4
/3
/2
/1
B0014
P653.1 (
0
)
B
B0012
P652.1 (
104)
B
B0010
P651.1 (
107)
B
M24
P24
-X101
B0104
B0107
Operation
0=
fault
*
)
*
)
1=
operation
No fault
*
)
P590 (
14)
B
Src BICO DSet
See P049.4
FSetp
Bit 1
P581.B
FSetp
Bit 0
P580.B
(f
or
T
contr
o
l)
(f
or
n/f contr
o
l or
v/f contr
o
l)