Technical Description
2-4
SITRANS FM Intermag 2 Flow Transmitter
Operating Manual - A5E00102775-03
Outputs and inputs
Electrical isolation
outputs electrically isolated from each other and from the
power supply, max. 60 V permissible against PE/PA
For 20 mA / HART devices (7ME5033-0xxxx and -2xxxx)
Analog output
Signal range
4 to 20 mA
Upper limit
20 to 22.5 mA
Failure signal
3.6 mA, 22 mA or 24 mA
Load
max. 600
Ω
Not intrinsically safe output
max. 600
Ω
, load voltage max. 15 V,
Intrinsically safe output (7ME5033-0BGxx)
max. 350
Ω
, load voltage max. 8,5 V,
For HART communikation,
≧
230
Ω
Communication
via analog output with PC coupling module or
HART communicator
Protocol
HART, Revision 5.1
Digital output 1
configurable for positive or negative logic
Signal
Non intrinsically safe output
configurable active or passive
Active
signal
DC 24 V,
≦
24 mA, Ri = 170
Ω
Passive signal
open collector, max. DC 30 V, 200 mA
Intrinsically safe output (7ME5033-0BGxx)
passive only
Signal
open collector, max. DC 30 V, 100 mA, 750 mW
Output configuration
Pulse
Significance
≦
5000 pulses/s
Pulse width
≧
0.1 ms
Frequency
≦
10,000 Hz
Limits
for flow and volume, flow direction, alarm
Digital output 2
Relay
NC or NO function
Rating
Non intrinsically safe output
max. 5 W, UC 30 V, 200 mA
Intrinsically safe output (7ME5033-0BGxx)
max. 5 W, UC 30 V, 100 mA, self resetting fuse, Ri
≦
9
Ω
Output configuration
limits for flow and volume, flow direction, alarm
Digital input (only alternative to digital output 2), not intrinsically safe
Input function
configurable high or low active,
measured value set to zero or counter reset
Signal voltage
max. 30 V, Re = 3 k
Ω
High level
+11 to 30 V
Low level
-30 to +5 V
for PROFIBUS devices (7ME5033-1xxxx)
PROFIBUS-PA
Communication
layer 1 and 2 according to PROFIBUS-PA
Transmission system
according to IEC 1158-2
Layer 7 (protocol layer)
according to PROFIBUS-PA and DP V1 (EN 50 170)
Device class
A,
Device profile
3.0; max. 4 simultaneous C2 connections
Bus voltage
Non instrinsically safe output
permissible 9 to 32 V
Intrinsically safe output (7ME5033-1BGxx)
permissible 9 to 24 V (FISCO supply device)
Current consumption from bus
10 mA, in the event of an error
≦
15 mA as result of
electrical current limiting
Digital output 1
Passive signal
configurable for positive or negative logic, open collector,
max. DC 30 V, 100 mA
Output configuration
Pulses
Pulse rate
≦
5000 pulses/s
Pulse width
≧
0.1 ms
Full scale frequency
≦
10,000 Hz
Limits
for flow and volume, flow direction, alarm
Содержание SITRANS F M Intermag 2
Страница 2: ......
Страница 8: ...SITRANS FM Intermag 2 Flow Transmitter Operating Manual A5E00102775 03 I 4 ...
Страница 9: ...1 1 SITRANS FM Intermag 2 Flow Transmitter Operating Manual A5E00102775 03 Information for the User 1 ...
Страница 111: ...Appendix 7 3 SITRANS FM Intermag 2 Flow Transmitter Operating Manual A5E00102775 03 ...
Страница 113: ...Appendix 7 5 SITRANS FM Intermag 2 Flow Transmitter Operating Manual A5E00102775 03 ...
Страница 114: ...Appendix 7 6 SITRANS FM Intermag 2 Flow Transmitter Operating Manual A5E00102775 03 ...
Страница 115: ...Appendix 7 7 SITRANS FM Intermag 2 Flow Transmitter Operating Manual A5E00102775 03 ...
Страница 116: ...Appendix 7 8 SITRANS FM Intermag 2 Flow Transmitter Operating Manual A5E00102775 03 ...
Страница 117: ...Appendix 7 9 SITRANS FM Intermag 2 Flow Transmitter Operating Manual A5E00102775 03 ...
Страница 118: ...Appendix 7 10 SITRANS FM Intermag 2 Flow Transmitter Operating Manual A5E00102775 03 ...
Страница 119: ...Appendix 7 11 SITRANS FM Intermag 2 Flow Transmitter Operating Manual A5E00102775 03 ...
Страница 120: ...Appendix 7 12 SITRANS FM Intermag 2 Flow Transmitter Operating Manual A5E00102775 03 ...
Страница 128: ...Appendix 7 20 SITRANS FM Intermag 2 Flow Transmitter Operating Manual A5E00102775 03 ...
Страница 129: ...Appendix 7 21 SITRANS FM Intermag 2 Flow Transmitter Operating Manual A5E00102775 03 ...