Operation
5-45
SITRANS FM Intermag 2 Flow Transmitter
Operating Manual - A5E00102775-03
The status bytes consist of three components:
S
Quality (the MSBs 6 and 7):
describes the basic quality of the corresponding measured value
S
Substatus (bits 2 to 5):
Differentiates the quality of the corresponding measured value
S
Limits (the LSBs 0 and 1):
indicate exceeding of the limit value
These components may adopt the following values in SITRANS FM:
Bit
7
Bit
6
Profile Designation
Meaning
0
0
bad
Useless measured value
0
1
uncertain
Uncertain measured value
1
0
good (not cascade)
Measured value OK
Table 5-7
Formats of the quality bits
Bit
5
Bit
4
Bit
3
Bit
2
Bezeichnung
Meaning
0
0
0
1
configuration error
Error in parameterization, i.e. upper and lower value for
measuring or output scale identical
0
0
1
0
not connected
Sensor error or sensor not connected
0
0
1
1
device failure
RAM or EEPROM defective;diagnostic bit ”Memory
error” is set additionally and diagnostic message ”RAM error”
or ”EEPROM error” displayed locally
0
1
1
1
out of service
Corresponding function block is in ”Out of service” mode
(see parameter ”MODE_BLK actual”)
0
0
0
0
non specific
Immersion check:
at least one electrode not immersed
0
0
0
1
last usable value
Failsafe operation: current measured value replaced by the last
good measured value
0
0
1
0
sunstitute set
Failsafe operation: current measured value replaced by the
agreed failsafe valuet
0
1
0
0
initial value
Failsafe operation or state before first measurement: actual
measured value replaced by start value
0
1
0
0
sensor conversion
not accurate
Measured value is outside the sensor limits
0
0
0
0
O.K.
Measured value is OK (normal state)
0
0
0
1
update event
A parameter with memory attribute ”static” was changed locally
or by PROFIBUS
0
0
1
0
active advisory alarm
Upper warning limit exceeded or lower
warning limit dropped below
0
1
0
0
active critical alarm
Upper alarm limit exceeded or lower
alarm limit dropped below
Table 5-8
Formats of the substatus bits
Содержание SITRANS F M Intermag 2
Страница 2: ......
Страница 8: ...SITRANS FM Intermag 2 Flow Transmitter Operating Manual A5E00102775 03 I 4 ...
Страница 9: ...1 1 SITRANS FM Intermag 2 Flow Transmitter Operating Manual A5E00102775 03 Information for the User 1 ...
Страница 111: ...Appendix 7 3 SITRANS FM Intermag 2 Flow Transmitter Operating Manual A5E00102775 03 ...
Страница 113: ...Appendix 7 5 SITRANS FM Intermag 2 Flow Transmitter Operating Manual A5E00102775 03 ...
Страница 114: ...Appendix 7 6 SITRANS FM Intermag 2 Flow Transmitter Operating Manual A5E00102775 03 ...
Страница 115: ...Appendix 7 7 SITRANS FM Intermag 2 Flow Transmitter Operating Manual A5E00102775 03 ...
Страница 116: ...Appendix 7 8 SITRANS FM Intermag 2 Flow Transmitter Operating Manual A5E00102775 03 ...
Страница 117: ...Appendix 7 9 SITRANS FM Intermag 2 Flow Transmitter Operating Manual A5E00102775 03 ...
Страница 118: ...Appendix 7 10 SITRANS FM Intermag 2 Flow Transmitter Operating Manual A5E00102775 03 ...
Страница 119: ...Appendix 7 11 SITRANS FM Intermag 2 Flow Transmitter Operating Manual A5E00102775 03 ...
Страница 120: ...Appendix 7 12 SITRANS FM Intermag 2 Flow Transmitter Operating Manual A5E00102775 03 ...
Страница 128: ...Appendix 7 20 SITRANS FM Intermag 2 Flow Transmitter Operating Manual A5E00102775 03 ...
Страница 129: ...Appendix 7 21 SITRANS FM Intermag 2 Flow Transmitter Operating Manual A5E00102775 03 ...