Functions
2.4 Single-Phase Overcurrent Protection
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
93
2.4.5
Settings
The table indicates region-specific default settings. Column C (configuration) indicates the corresponding sec-
ondary nominal current of the current transformer.
2.4.6
Information List
Addr.
Parameter
C
Setting Options
Default Setting
Comments
2701
50 1Ph
OFF
ON
OFF
50 1Ph
2702
50 1Ph-2 PICKUP
1A
0.05 .. 35.00 A;
∞
0.50 A
50 1Ph-2 Pickup
5A
0.25 .. 175.00 A;
∞
2.50 A
2703
50 1Ph-2 PICKUP
0.003 .. 1.500 A;
∞
0.300 A
50 1Ph-2 Pickup
2704
50 1Ph-2 DELAY
0.00 .. 60.00 sec;
∞
0.10 sec
50 1Ph-2 Time Delay
2705
50 1Ph-1 PICKUP
1A
0.05 .. 35.00 A;
∞
0.20 A
50 1Ph-1 Pickup
5A
0.25 .. 175.00 A;
∞
1.00 A
2706
50 1Ph-1 PICKUP
0.003 .. 1.500 A;
∞
0.100 A
50 1Ph-1 Pickup
2707
50 1Ph-1 DELAY
0.00 .. 60.00 sec;
∞
0.50 sec
50 1Ph-1 Time Delay
No.
Information
Type of In-
formation
Comments
5951
>BLK 50 1Ph
SP
>BLOCK 50 1Ph
5952
>BLK 50 1Ph-1
SP
>BLOCK 50 1Ph-1
5953
>BLK 50 1Ph-2
SP
>BLOCK 50 1Ph-2
5961
50 1Ph OFF
OUT
50 1Ph is OFF
5962
50 1Ph BLOCKED
OUT
50 1Ph is BLOCKED
5963
50 1Ph ACTIVE
OUT
50 1Ph is ACTIVE
5966
50 1Ph-1 BLK
OUT
50 1Ph-1 is BLOCKED
5967
50 1Ph-2 BLK
OUT
50 1Ph-2 is BLOCKED
5971
50 1Ph Pickup
OUT
50 1Ph picked up
5972
50 1Ph TRIP
OUT
50 1Ph TRIP
5974
50 1Ph-1 PU
OUT
50 1Ph-1 picked up
5975
50 1Ph-1 TRIP
OUT
50 1Ph-1 TRIP
5977
50 1Ph-2 PU
OUT
50 1Ph-2 picked up
5979
50 1Ph-2 TRIP
OUT
50 1Ph-2 TRIP
5980
50 1Ph I:
VI
50 1Ph: I at pick up
Содержание SIPROTEC 7SJ61
Страница 368: ...Technical Data 4 22 Dimensions SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 368 ...
Страница 436: ...Appendix A 11 Measured Values SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 436 ...
Страница 438: ...Literature SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 438 ...
Страница 450: ...Glossary SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 450 ...
Страница 454: ...Index SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 454 ...