Functions
2.3 Dynamic Cold Load Pickup
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
81
2.3.3
Settings
The table indicates region-specific default settings. Column C (configuration) indicates the corresponding sec-
ondary nominal current of the current transformer.
Addr.
Parameter
C
Setting Options
Default Setting
Comments
1701
COLDLOAD PICKUP
OFF
ON
OFF
Cold-Load-Pickup Func-
tion
1702
Start Condition
No Current
Breaker Contact
79 ready
No Current
Start Condition
1703
CB Open Time
0 .. 21600 sec
3600 sec
Circuit Breaker OPEN
Time
1704
Active Time
1 .. 21600 sec
3600 sec
Active Time
1705
Stop Time
1 .. 600 sec;
∞
600 sec
Stop Time
1801
50c-2 PICKUP
1A
0.10 .. 35.00 A;
∞
10.00 A
50c-2 Pickup
5A
0.50 .. 175.00 A;
∞
50.00 A
1802
50c-2 DELAY
0.00 .. 60.00 sec;
∞
0.00 sec
50c-2 Time Delay
1803
50c-1 PICKUP
1A
0.10 .. 35.00 A;
∞
2.00 A
50c-1 Pickup
5A
0.50 .. 175.00 A;
∞
10.00 A
1804
50c-1 DELAY
0.00 .. 60.00 sec;
∞
0.30 sec
50c-1 Time Delay
1805
51c PICKUP
1A
0.10 .. 4.00 A
1.50 A
51c Pickup
5A
0.50 .. 20.00 A
7.50 A
1806
51c TIME DIAL
0.05 .. 3.20 sec;
∞
0.50 sec
51c Time dial
1807
51c TIME DIAL
0.50 .. 15.00 ;
∞
5.00
51c Time dial
1808
50c-3 PICKUP
1A
1.00 .. 35.00 A;
∞
∞
A
50c-3 Pickup
5A
5.00 .. 175.00 A;
∞
∞
A
1809
50c-3 DELAY
0.00 .. 60.00 sec;
∞
0.00 sec
50c-3 Time Delay
1901
50Nc-2 PICKUP
1A
0.05 .. 35.00 A;
∞
7.00 A
50Nc-2 Pickup
5A
0.25 .. 175.00 A;
∞
35.00 A
1902
50Nc-2 DELAY
0.00 .. 60.00 sec;
∞
0.00 sec
50Nc-2 Time Delay
1903
50Nc-1 PICKUP
1A
0.05 .. 35.00 A;
∞
1.50 A
50Nc-1 Pickup
5A
0.25 .. 175.00 A;
∞
7.50 A
1904
50Nc-1 DELAY
0.00 .. 60.00 sec;
∞
0.30 sec
50Nc-1 Time Delay
1905
51Nc PICKUP
1A
0.05 .. 4.00 A
1.00 A
51Nc Pickup
5A
0.25 .. 20.00 A
5.00 A
1906
51Nc T-DIAL
0.05 .. 3.20 sec;
∞
0.50 sec
51Nc Time Dial
1907
51Nc T-DIAL
0.50 .. 15.00 ;
∞
5.00
51Nc Time Dial
1908
50Nc-3 PICKUP
0.25 .. 35.00 A;
∞
∞
A
50Nc-3 Pickup
1909
50Nc-3 DELAY
0.00 .. 60.00 sec;
∞
0.00 sec
50Nc-3 Time Delay
Содержание SIPROTEC 7SJ61
Страница 368: ...Technical Data 4 22 Dimensions SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 368 ...
Страница 436: ...Appendix A 11 Measured Values SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 436 ...
Страница 438: ...Literature SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 438 ...
Страница 450: ...Glossary SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 450 ...
Страница 454: ...Index SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 454 ...