Technical Data
4.19 User-defined Functions (CFC)
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
359
Processing Times in TICKS Required by the Individual Elements
Individual Element
Number of TICKS
Block, basic requirement
5
Each input more than 3 inputs for generic modules
1
Connection to an input signal
6
Connection to an output signal
7
Additional for each chart
1
Arithmetic
ABS_VALUE
5
ADD
26
SUB
26
MUL
26
DIV
54
SQUARE_ROOT
83
Basic logic
AND
5
CONNECT
4
DYN_OR
6
NAND
5
NEG
4
NOR
5
OR
5
RISE_DETECT
4
X_OR
5
Information status
SI_GET_STATUS
5
CV_GET_STATUS
5
DI_GET_STATUS
5
MV_GET_STATUS
5
SI_SET_STATUS
5
DI_SET_STATUS 5
MV_SET_STATUS
5
ST_AND
5
ST_OR
5
ST_NOT
5
Memory
D_FF
5
D_FF_MEMO
6
RS_FF
4
RS_FF_MEMO
4
SR_FF
4
SR_FF_MEMO
4
Control commands
BOOL_TO_CO
5
BOOL_TO_IC
5
CMD_INF
4
CMD_CHAIN
34
CMD_CANCEL
3
LOOP
8
Содержание SIPROTEC 7SJ61
Страница 368: ...Technical Data 4 22 Dimensions SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 368 ...
Страница 436: ...Appendix A 11 Measured Values SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 436 ...
Страница 438: ...Literature SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 438 ...
Страница 450: ...Glossary SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 450 ...
Страница 454: ...Index SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 454 ...