Input/Output Board A–I/O-2 for 7SJ61.../EE
The layout of the printed circuit board for the input/output board A–I/O-2 is illustrated in the following Figure.
The set nominal currents of the current input transformers and the selected operating voltage of binary inputs
BI4 to BI11 are checked.
Figure 3-7
Input/output module A–I/O-2 for devices (releases .../EE and higher) with representation of the
jumper settings required for the board configuration
The jumpers X60 to X63 must all be set to the same rated current, i.e. one jumper (X61 to X63) for each input
transformer and in addition the common jumper X60. The jumper X64 determines the rated current for the input
I
N
and may thus have a setting that deviates from that of the phase currents. In models with sensitive ground
fault current input there is no jumper X64.
Jumpers X21 to X28 do not exist in device versions 7SJ610*-.