Functions
2.2 Overcurrent Protection 50, 51, 50N, 51N
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
63
Figure 2-13
Reverse interlocking protection scheme
2.2.10
Setting Notes
General
When selecting the time overcurrent protection in DIGSI a dialog box appears with several tabs, such as , , , ,
and in which the individual parameters can be set. Depending on the functional scope specified during config-
uration of the protective functions in addresses
112
Charac. Phase
and
113
Charac. Ground
the number
of tabs can vary. If address
FCT 50/51
was set to
Definite Time
, or
Charac. Ground
was set to
Definite Time
, then only the settings for the definite time elements are available. The selection of
TOC IEC
or
TOC ANSI
makes additional inverse characteristics available. The superimposed high-set elements 50-2,
50-3 and 50N-2, 50N-3 are available in all these cases.
Parameter
250
50/51 2-ph prot
can also be set to activate two-phase overcurrent protection.
Under address
1201
FCT 50/51
, overcurrent protection for phases and under address
1301
FCT 50N/51N
,
the ground overcurrent protection can be switched
ON
or
OFF
.
Pickup values, time delays, and characteristics for ground protection are set separately from the pickup values,
time delays and characteristic curves associated with phase protection. Because of this, relay coordination for
ground faults is independent of relay coordination for phase faults, and more sensitive settings can often be
applied to directional ground protection.
Depending on the setting of parameter
251
CT Connect.
, the device can also be used in specific system
constellations with regard to current connections. Further information can be found under Section 2.1.3.2 ,
“Current Connections“.
Содержание SIPROTEC 7SJ61
Страница 368: ...Technical Data 4 22 Dimensions SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 368 ...
Страница 436: ...Appendix A 11 Measured Values SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 436 ...
Страница 438: ...Literature SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 438 ...
Страница 450: ...Glossary SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 450 ...
Страница 454: ...Index SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 454 ...