Functions
2.8 Monitoring Functions
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
145
Table 2-6
Summary of malfunction responses by the protection relay
1)
After three unsuccessful restarts, the device is taken out of service.
2)
DOK = "Device Okay" = Ready for service relay drops off, protection and control functions are blocked.
Monitoring
Possible Causes
Malfunction Re-
sponse
Message (No.)
Output
Auxiliary supply voltage loss
External (aux. volt-
age), internal (con-
verter)
Device shutdown
All LEDs dark
DOK
drops
out
Internal supply voltages
Internal (power
supply)
Device shutdown
LED "ERROR"
DOK
drops
out
Back-up battery
Internal (battery)
Message
„Fail Battery“ (177)
Hardware watchdog
Internal (processor
failure)
Device shutdown
LED "ERROR"
DOK
drops
out
Software watchdog
Internal (processor
failure)
Restart attempt
LED "ERROR"
DOK
drops
out
Working memory
Internal (hardware)
Relay aborts restart,
device shutdown
LED flashes
DOK
drops
out
Program memory
Internal (hardware)
During startup
LED "ERROR"
DOK
drops
out
During operation:
Restart attempt
LED "ERROR"
Settings
Internal (hardware)
Restart attempt
LED "ERROR"
DOK
drops
out
Scanning frequency
Internal (hardware)
Device shutdown
LED "ERROR"
DOK
drops
out
Measured value acquisition
External (hardware)
Blocking by the protec-
tion function
„Error A/D-conv.“ (181),
LED ”ERROR"
DOK
drops
out
Error in the I/O-board
Internal (hardware)
Device shutdown
„I/O-Board error“ (178),
LED "ERROR"
DOK
drops
out
Module error
Internal (hardware)
Device shutdown
„Error Board 1“ to „Error
Board 7“ (178 to 189),
LED "ERROR"
DOK
drops
out
Internal auxiliary voltage 5 V
Internal (hardware)
Device shutdown
„Error 5V“ (144),
LED "ERROR"
DOK
drops
out
0 V-Monitoring
Internal (hardware)
Device shutdown
„Error 0V“ (145),
LED "ERROR"
DOK
drops
out
Internal auxiliary voltage -5 V
Internal (hardware)
Device shutdown
„Error -5V“ (146),
LED "ERROR"
DOK
drops
out
Offset Monitoring
Internal (Hardware)
Device shutdown
„Error Offset“ (191)
DOK
drops
out
Internal supply voltages
Internal (hardware)
Device shutdown
„Error PwrSupply“
(147),
LED "ERROR"
DOK
drops
out
Current sum
Internal (measured
value acquisition)
Message
„Failure
Σ
I“ (162)
As allocated
Current symmetry
External (power
system or current
transformer)
Message
„Fail I balance“ (163)
As allocated
Current rotation
External (power
system or connection)
Message
„Fail Ph. Seq. I“ (175)
As allocated
Trip circuit monitoring
External (trip circuit or
control voltage)
Message
„74TC Trip cir.“ (6865)
As allocated
Calibration data fault
Internal (Hardware)
Message
„Alarm NO calibr“ (193) As allocated
Содержание SIPROTEC 7SJ61
Страница 368: ...Technical Data 4 22 Dimensions SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 368 ...
Страница 436: ...Appendix A 11 Measured Values SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 436 ...
Страница 438: ...Literature SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 438 ...
Страница 450: ...Glossary SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 450 ...
Страница 454: ...Index SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 454 ...