Functions
2.9 Ground Fault Protection 50N(s), 51N(s)
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
152
Figure 2-52
Trip-time characteristics of the inverse-time ground fault protection 51Ns with logarithmic
inverse characteristic with knee point (example for 51Ns = 0.004 A)
User Defined characteristics (Inverse Time)
If a user-defined characteristic is configured at address
131
,
Sens. Gnd Fault
User Defined PU
, it should
be noted that there is a safety factor of 1.1 between pickup and setting value - as is standard for inverse curves.
This means that pickup will only be initiated when current of 1.1 times the setting value flows.
Entry of the value pair (current and time) is a multiple of the settings at addresses
3119
51Ns PICKUP
and
3120
51NsTIME DIAL
. Therefore, it is recommended that these addresses are initially set to 1.00 for simplic-
ity. Once the curve is entered, the settings at addresses
3119
and/or
3120
may be modified if necessary.
The default setting of current values is
∞
. They are, therefore, not enabled — and no pickup or tripping of these
protective functions will occur.
Up to 20 pairs of values (current and time) may be entered at address
3131
M.of PU TD
. The device then
approximates the characteristic, using linear interpolation.
The following must be observed:
• The value pairs should be entered in increasing sequence. Fewer than 20 pairs is also sufficient. In most
cases, about 10 pairs is sufficient to define the characteristic accurately. A value pair which will not be used
has to be made invalid by entering "
∞
” for the threshold! The user must ensure the value pairs produce a
clear and constant characteristic.
The current values entered should be those from Table 2-3, along with the matching times. Deviating values
MofPU (multiples of PU-values) are rounded. This, however, will not be indicated.
Currents less than the smallest current value entered will not lead to an extension of the tripping time. The
pickup curve (see Figure 2-53) continues, from the smallest current point parallel to the current axis.
Currents greater than the highest current value entered will not lead to a reduction of the tripping time. The
pickup curve (see Figure 2-53) continues, from the largest current point parallel to the current axis.
Содержание SIPROTEC 7SJ61
Страница 368: ...Technical Data 4 22 Dimensions SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 368 ...
Страница 436: ...Appendix A 11 Measured Values SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 436 ...
Страница 438: ...Literature SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 438 ...
Страница 450: ...Glossary SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 450 ...
Страница 454: ...Index SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 454 ...