Technical Data
4.13 Ground Fault Protection 50N(s), 51N(s)
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
348
Logarithmic Inverse Trip Time Characteristics
Figure 4-11
Trip time characteristics of inverse time ground fault protection with logarithmic inverse char-
acteristic
Logarithmic inverse
t = 51Ns MAX. TIME DIAL - 51Ns TIME DIAL·ln(
I
/
51Ns PICKUP
)
Note:
For
I
/
51Ns PICKUP
> 35 the time applies for
I
/
51Ns PICKUP
= 35