If performance makes it necessary to switch several varistors in parallel, preference should by given to types
with a flat characteristic to avoid asymmetrical loading. therefore recommend the following types from
METROSIL:
600A/S1/S256 (k = 450,
β
= 0.25)
600A/S1/S1088 (k = 900,
β
= 0.25)
The pickup value (0.1 A or 0.05 A in the example) is set in address
2706
50 1Ph-1 PICKUP
in the device.
The 50-2 element is not required (address
2703
50 1Ph-2 PICKUP
=
∞
).
The trip command of the protection can be delayed via address
2707
50 1Ph-1 DELAY
. Normally, such delay
is set to
0
.
If a higher number of CTs is connected in parallel, e.g. as busbar protection with several feeders, the magne-
tizing currents of the transformers connected in parallel cannot be neglected anymore. In this case, the mag-
netizing currents at half the knee-point voltage (corresponds to the setting value) have to be summed up. These
magnetizing currents reduce the current through the resistor R. Therefore the actual pickup value will be cor-
respondingly higher.
Application as Tank Leakage Protection
The use as tank leakage protection requires that a sensitive input transformer is available at the device input
I
N
/
I
NS
. In this case, only the pickup value for single phase overcurrent protection is set at the 7SJ61 device for
the current at input
I
N
/
I
NS
.
The tank leakage protection is a sensitive overcurrent protection which detects the leakage current between
the isolated transformer tank and ground. Its sensitivity is set in address
2706
50 1Ph-1 PICKUP
. The 50-2
element is not required (address
2703
50 1Ph-2 PICKUP
=
∞
).
The trip command of the element can be delayed in address
2707
50 1Ph-1 DELAY
. It is normally set to
0
.
Note
In the following settings, addresses
2703
and
2706
are valid for a highly sensitive current measuring input in-
dependently of the nominal current.
Содержание SIPROTEC 7SJ61
Страница 368: ...Technical Data 4 22 Dimensions SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 368 ...
Страница 436: ...Appendix A 11 Measured Values SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 436 ...
Страница 438: ...Literature SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 438 ...
Страница 450: ...Glossary SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 450 ...
Страница 454: ...Index SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 454 ...