Functions
2.11 Automatic Reclosing System 79
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
177
Dead Times (1st AR)
Addresses
7127
and
7128
are used to determine the duration of the dead times of the 1st cycle. The time
defined by this parameter is started when the circuit breaker opens (if auxiliary contacts are allocated) or when
the pickup drops out following the trip command of a starter. Dead time before first auto-reclosure for reclosing
program "Phase" is set in address
7127
DEADTIME 1: PH
, for reclosing program "ground" in address
7128
DEADTIME 1: G
. The exact definition of the programs is described in the functional description at margin
heading "Reclosing Programs". The length of the dead time should relate to the type of application. With longer
lines they should be long enough to make sure that the fault arc disappears and that the air surrounding it is
de-ionized and auto-reclosure can successfully take place (usually 0.9 s to 1.5 s). For lines supplied by more
than one side, mostly system stability has priority. Since the de-energized line cannot transfer synchronizing
energy, only short dead times are allowed. Standard values are 0.3 s to 0.6 s. In radial systems longer dead
times are allowed.
Cyclic Control of Protective Functions via Automatic Reclosure
Addresses
7200
to
7205
as well as
7248
and
7249
allow cyclic control of the various protection functions by
the automatic reclosing function. Thus protective elements can be blocked selectively, made to operate instan-
taneously or according to the configured delay times. The following options are available:
The following options are available:
•
Set value T=T
The protective element is delayed as configured i.e., the auto-reclose function does not
effect this element;
instant. T=0
The protective element becomes instantaneous if the auto-reclose function is ready to
perform the mentioned cycle;
blocked T=
∞
The protective element is blocked if the auto-reclose function reaches the cycle defined in
the parameter.
Dead Times (2nd to 4th AR)
If more than one reclosing cycle was set, you can now configure the individual reclosing settings for the 2nd to
4th cycle. The same options are available as for the first cycle.
For the 2nd cycle:
For the 3rd cycle:
For the 4th cycle:
Address 7129
DEADTIME 2: PH
Dead time for the 2nd reclosing attempt "Phase"
Address 7130
DEADTIME 2: G
Dead time for the 2nd reclosing attempt "Ground"
Addresses 7212
to 7217
allow cyclic control of the various protective functions by the
2nd reclosing attempt
Address 7131
DEADTIME 3: PH
Dead time for the 3rd reclosing attempt "Phase"
Address 7132
DEADTIME 3: G
Dead time for the 3rd reclosing attempt "Ground"
Addresses 7224
to 7229
allow cyclic control of the various protective functions by the
3rd reclosing attempt
Address 7133
DEADTIME 4: PH
Dead time for the 4th reclosing attempt "Phase"
Address 7134
DEADTIME 4: G
Dead time for the 4th reclosing attempt "Ground"
Addresses 7236
to 7241
allow cyclic control of the various protective functions by the
4th reclosing attempt
Содержание SIPROTEC 7SJ61
Страница 368: ...Technical Data 4 22 Dimensions SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 368 ...
Страница 436: ...Appendix A 11 Measured Values SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 436 ...
Страница 438: ...Literature SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 438 ...
Страница 450: ...Glossary SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 450 ...
Страница 454: ...Index SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 454 ...