Mounting and Commissioning
3.3 Commissioning
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
292
Structure of the Test Dialog Box
In the column
Indication
the display texts of all indications are displayed which were allocated to the system
interface in the matrix. In the column
SETPOINT Status
the user has to define the value for the messages to
be tested. Depending on annunciation type, several input fields are offered (e.g. message
„ON“
/ message
„OFF“
). By clicking on one of the fields you can select the desired value from the pull-down menu.
Figure 3-19
System interface test with the dialog box: Creating messages - example
Changing the Operating State
When clicking one of the buttons in the column
Action
for the first time, you will be prompted for the password
no. 6 (for hardware test menus). After correct entry of the password, individual annunciations can be initiated.
To do so, click on the button
Send
on the corresponding line. The corresponding message is issued and can
be read out either from the event log of the SIPROTEC 4 device or from the substation control system.
As long as the window is open, further tests can be performed.
Test in Message Direction
For all information that is transmitted to the central station, test the options in the list which appears in
SET-
POINT Status
:
• Make sure that each checking process is carried out carefully without causing any danger (see above and
refer to DANGER!)
• Click on Send in the function to be tested and check whether the transmitted information reaches the central
station and shows the desired reaction. Data which are normally linked via binary inputs (first character „>“)
are likewise indicated to the central power system with this procedure. The function of the binary inputs itself
is tested separately.
Exiting the Test Mode
To end the System Interface Test, click on
Close
. The device is briefly out of service while the start-up routine
is executed. The dialog box closes.
Содержание SIPROTEC 7SJ61
Страница 368: ...Technical Data 4 22 Dimensions SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 368 ...
Страница 436: ...Appendix A 11 Measured Values SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 436 ...
Страница 438: ...Literature SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 438 ...
Страница 450: ...Glossary SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 450 ...
Страница 454: ...Index SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 454 ...