Functions
2.1 General
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
46
2.1.6.3
Settings
The table indicates region-specific default settings. Column C (configuration) indicates the corresponding sec-
ondary nominal current of the current transformer.
2.1.6.4
Information List
Addr.
Parameter
C
Setting Options
Default Setting
Comments
1102
FullScaleCurr.
10 .. 50000 A
100 A
Measurem:FullScaleCur-
rent(Equipm.rating)
1107
I MOTOR START
1A
0.40 .. 10.00 A
2.50 A
Motor Start Current (Block
49, Start 48)
5A
2.00 .. 50.00 A
12.50 A
No.
Information
Type of In-
formation
Comments
126
ProtON/OFF
IntSP
Protection ON/OFF (via system port)
356
>Manual Close
SP
>Manual close signal
501
Relay PICKUP
OUT
Relay PICKUP
511
Relay TRIP
OUT
Relay GENERAL TRIP command
533
Ia =
VI
Primary fault current Ia
534
Ib =
VI
Primary fault current Ib
535
Ic =
VI
Primary fault current Ic
561
Man.Clos.Detect
OUT
Manual close signal detected
2720
>Enable ANSI#-2
SP
>Enable 50/67-(N)-2 (override 79 blk)
4601
>52-a
SP
>52-a contact (OPEN, if bkr is open)
4602
>52-b
SP
>52-b contact (OPEN, if bkr is closed)
16019
>52 Wear start
SP
>52 Breaker Wear Start Criteria
16020
52 WearSet.fail
OUT
52 Wear blocked by Time Setting Failure
16027
52WL.blk I PErr
OUT
52 Breaker Wear Logic blk Ir-CB>=Isc-CB
16028
52WL.blk n PErr
OUT
52 Breaker W.Log.blk SwCyc.Isc>=SwCyc.Ir
Содержание SIPROTEC 7SJ61
Страница 368: ...Technical Data 4 22 Dimensions SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 368 ...
Страница 436: ...Appendix A 11 Measured Values SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 436 ...
Страница 438: ...Literature SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 438 ...
Страница 450: ...Glossary SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 450 ...
Страница 454: ...Index SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 454 ...