Functions
2.11 Automatic Reclosing System 79
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
176
Figure 2-60
CFC logic for Manual Close with automatic reclosing via control
The selection list for parameter
7137
is created dynamically depending on the allocated switchgear compo-
nents. If one of the switchgear components is selected, usually the circuit breaker
„52Breaker“
, reclosure is
accomplished via control. In this case, the automatic reclosure function does not create a close command but
issues a close request. It is forwarded to the control which then takes over the switching. Thus, the properties
defined for the switchgear component such as interlocking and command times apply. Hence, it is possible that
the close command will not be carried out due to an applying interlocking condition.
If this behavior is not desired, the auto-reclose function can also generate the close command
„79 Close“
directly which must be allocated to the associated contact. The CFC Chart as in Figure 2-60 is not needed in
this case.
Auto-Reclosing with External Synchrocheck
Parameter
7139
External SYNC
can be set to determine that the auto-reclose function operates with exter-
nal synchrocheck. External synchronization is possible if the parameter is set to
YES
and 7SJ61 is linked to the
external synchrocheck via the message 2865
„79 Sync.Request“
and the binary input
„>Sync.release“
.
Initiation and Blocking of Automatic Reclosure by Protective Elements (configuration)
At addresses
7150
to
7167
, reclosing can be initiated or blocked for various types of protection functions. They
constitute the interconnection between protection elements and auto-reclose function. Each address desig-
nates a protection function together with its ANSI synonym, e.g.
50-2
for the high-set element of the non-di-
rectional time overcurrent protection (address
7152
).
The setting options have the following meaning:
•
Starts 79
The protective element initiates the automatic reclosure via its trip command;
No influence
the protective element does not start the automatic reclosure, it may however be initiated
by other functions;
Stops 79
the protective element blocks the automatic reclosure, it cannot be started by other functions; a
dynamic blocking is initiated.
Содержание SIPROTEC 7SJ61
Страница 368: ...Technical Data 4 22 Dimensions SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 368 ...
Страница 436: ...Appendix A 11 Measured Values SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 436 ...
Страница 438: ...Literature SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 438 ...
Страница 450: ...Glossary SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 450 ...
Страница 454: ...Index SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 454 ...