Functions
2.2 Overcurrent Protection 50, 51, 50N, 51N
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
74
1316A
50N-3 active
Always
with 79 active
Always
50N-3 active
1317
50N-3 PICKUP
0.25 .. 35.00 A;
∞
∞
A
50N-3 Pickup
1318
50N-3 DELAY
0.00 .. 60.00 sec;
∞
0.00 sec
50N-3 Time Delay
1319A
50N-3 measurem.
Fundamental
True RMS
Instantaneous
Fundamental
50N-3 measurement of
1320A
50N-2 measurem.
Fundamental
True RMS
Fundamental
50N-2 measurement of
1321A
50N-1 measurem.
Fundamental
True RMS
Fundamental
50N-1 measurement of
1322A
51N measurem.
Fundamental
True RMS
Fundamental
51N measurement of
1330
50N/51N
1.00 .. 20.00 I/Ip;
∞
0.01 .. 999.00 TD
50N/51N
1331
MofPU Res T/TEp
0.05 .. 0.95 I/Ip;
∞
0.01 .. 999.00 TD
Multiple of Pickup <->
T/TEp
2201
INRUSH REST.
OFF
ON
OFF
Inrush Restraint
2202
2nd HARMONIC
10 .. 45 %
15 %
2nd. harmonic in % of fun-
damental
2203
CROSS BLOCK
NO
YES
NO
Cross Block
2204
CROSS BLK TIMER
0.00 .. 180.00 sec
0.00 sec
Cross Block Time
2205
I Max
1A
0.30 .. 25.00 A
7.50 A
Maximum Current for
Inrush Restraint
5A
1.50 .. 125.00 A
37.50 A
Addr.
Parameter
C
Setting Options
Default Setting
Comments
Содержание SIPROTEC 7SJ61
Страница 368: ...Technical Data 4 22 Dimensions SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 368 ...
Страница 436: ...Appendix A 11 Measured Values SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 436 ...
Страница 438: ...Literature SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 438 ...
Страница 450: ...Glossary SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 450 ...
Страница 454: ...Index SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 454 ...