Appendix
A.8 Settings
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
409
7135
# OF RECL. GND
79M Auto Recl.
0 .. 9
1
Number of Reclosing Cycles
Ground
7136
# OF RECL. PH
79M Auto Recl.
0 .. 9
1
Number of Reclosing Cycles
Phase
7137
Cmd.via control
79M Auto Recl.
(Setting options depend
on configuration)
None
Close command via control
device
7139
External SYNC
79M Auto Recl.
YES
NO
NO
External 25 synchronisation
7140
ZONE SEQ.COORD.
79M Auto Recl.
OFF
ON
OFF
ZSC - Zone sequence coordina-
tion
7150
50-1
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
50-1
7151
50N-1
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
50N-1
7152
50-2
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
50-2
7153
50N-2
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
50N-2
7154
51
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
51
7155
51N
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
51N
7162
sens Ground Flt
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
(Sensitive) Ground Fault
7163
46
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
46
7164
BINARY INPUT
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
Binary Input
7165
3Pol.PICKUP BLK
79M Auto Recl.
YES
NO
NO
3 Pole Pickup blocks 79
7166
50-3
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
50-3
7167
50N-3
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
50N-3
7200
bef.1.Cy:50-1
79M Auto Recl.
Set value T=T
instant. T=0
blocked T=
∞
Set value T=T
before 1. Cycle: 50-1
7201
bef.1.Cy:50N-1
79M Auto Recl.
Set value T=T
instant. T=0
blocked T=
∞
Set value T=T
before 1. Cycle: 50N-1
7202
bef.1.Cy:50-2
79M Auto Recl.
Set value T=T
instant. T=0
blocked T=
∞
Set value T=T
before 1. Cycle: 50-2
7203
bef.1.Cy:50N-2
79M Auto Recl.
Set value T=T
instant. T=0
blocked T=
∞
Set value T=T
before 1. Cycle: 50N-2
7204
bef.1.Cy:51
79M Auto Recl.
Set value T=T
instant. T=0
blocked T=
∞
Set value T=T
before 1. Cycle: 51
7205
bef.1.Cy:51N
79M Auto Recl.
Set value T=T
instant. T=0
blocked T=
∞
Set value T=T
before 1. Cycle: 51N
7212
bef.2.Cy:50-1
79M Auto Recl.
Set value T=T
instant. T=0
blocked T=
∞
Set value T=T
before 2. Cycle: 50-1
7213
bef.2.Cy:50N-1
79M Auto Recl.
Set value T=T
instant. T=0
blocked T=
∞
Set value T=T
before 2. Cycle: 50N-1
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments
Содержание SIPROTEC 7SJ61
Страница 368: ...Technical Data 4 22 Dimensions SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 368 ...
Страница 436: ...Appendix A 11 Measured Values SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 436 ...
Страница 438: ...Literature SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 438 ...
Страница 450: ...Glossary SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 450 ...
Страница 454: ...Index SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 454 ...