Functions
2.17 Auxiliary Functions
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
231
2.17.4.4 Information List
2.17.5
Min/Max Measurement Setup
Minimum and maximum values are calculated by the 7SJ61. Time and date of the last update of the values can
also be read out.
2.17.5.1 Description
Minimum and Maximum Values
The minimum and maximum values of the three phase currents
I
A
,
I
B
,
I
C
, the positive sequence components
I
1
and the thermal measured value of overload protection
Θ
/
Θ
Trip
are calculated as primary values including the
date and time they were last updated.
The minimum and maximum values of the long-term mean values listed in the previous section are also calcu-
lated.
The min/max values can be reset via binary inputs, via DIGSI or via the integrated control panel at any time. In
addition, the reset can also take place cyclically, beginning with a pre-selected point in time.
2.17.5.2 Setting Notes
Minimum and Maximum Values
The tracking of minimum and maximum values can be reset automatically at a programmable point in time. To
select this feature, address
8311
MinMax cycRESET
should be set to
YES
. The point in time when reset is to
take place (the minute of the day in which reset will take place) is set at address
8312
MiMa RESET TIME
.
The reset cycle in days is entered at address
8313
MiMa RESETCYCLE
, and the beginning date of the cyclical
process, from the time of the setting procedure (in days), is entered at address
8314
MinMaxRES.START
.
2.17.5.3 Settings
No.
Information
Type of In-
formation
Comments
833
I1 dmd=
MV
I1 (positive sequence) Demand
963
Ia dmd=
MV
I A demand
964
Ib dmd=
MV
I B demand
965
Ic dmd=
MV
I C demand
Addr.
Parameter
Setting Options
Default Setting
Comments
8311
MinMax cycRESET
NO
YES
YES
Automatic Cyclic Reset Function
8312
MiMa RESET TIME
0 .. 1439 min
0 min
MinMax Reset Timer
8313
MiMa RESETCYCLE
1 .. 365 Days
7 Days
MinMax Reset Cycle Period
8314
MinMaxRES.START
1 .. 365 Days
1 Days
MinMax Start Reset Cycle in
Содержание SIPROTEC 7SJ61
Страница 368: ...Technical Data 4 22 Dimensions SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 368 ...
Страница 436: ...Appendix A 11 Measured Values SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 436 ...
Страница 438: ...Literature SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 438 ...
Страница 450: ...Glossary SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 450 ...
Страница 454: ...Index SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 454 ...