Functions
2.9 Ground Fault Protection 50N(s), 51N(s)
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
151
Logarithmic Inverse characteristic (Inverse Time)
The logarithmic inverse characteristic (see Figure 2-51) is set in parameters
3119
51Ns PICKUP
,
3141
51Ns
Tmax
,
3140
51Ns Tmin
,
3142
51Ns TIME DIAL
and
3143
51Ns Startpoint
.
51Ns Tmin
and
51Ns
Tmax
define the tripping time range. The slope of the curve is defined by
3142
51Ns TIME DIAL
.
51Ns
PICKUP
is the reference value for all current values with
51Ns Startpoint
representing the beginning of the
curve, i.e. the lower operating range on the current axis (referred to
51Ns PICKUP
). This factor is preset to the
value 1.1, analogously to the other inverse time curves. This factor can also be set to 1.0 since in logarithmic
inverse curves the tripping time on a current value, which is identical to the specified pickup threshold, does
not go towards infinity, but has a finite time value.
Figure 2-51
Trip time characteristics of inverse time ground fault protection with logarithmic inverse charac-
teristic
Logarithmic inverse
t = 51Ns MAX. TIME DIAL - 51Ns TIME DIAL·ln(
I
/
51Ns PICKUP
)
Note:
For
I
/
51Ns PICKUP
> 35 the time applies for
I
/
51Ns PICKUP
= 35
Logarithmic Inverse characteristic with Knee Point (inverse time)
The logarithmic inverse curve with knee point (see figure 2-52) is set with the parameters
3119
51Ns PICKUP
,
3127
51Ns I T min
,
3128
51Ns I T knee
,
3132
51Ns TD
,
3140
51Ns T min
and
3141
51Ns T max
.
51Ns T min
and
51Ns T max
determine the tripping time range with
51Ns T max
of the current threshold
51Ns PICKUP
and
51Ns T min
of the current threshold
51Ns I T min
assigned. When configuring the
knee point time
51Ns T knee
, the tripping time is determined at transition of the two curve sections with dif-
ferent slopes. The point of transition is defined by the current threshold
51Ns I T knee
.
51Ns PICKUP
rep-
resents the minimum pickup limit for the ground fault pickup current of the overcurrent element. After a
maximum secondary current of 1.4 A has been reached, the tripping time assumes a constant value. Parameter
51Ns TD
serves as a time multiplier for multiplication of the tripping time.
Содержание SIPROTEC 7SJ61
Страница 368: ...Technical Data 4 22 Dimensions SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 368 ...
Страница 436: ...Appendix A 11 Measured Values SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 436 ...
Страница 438: ...Literature SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 438 ...
Страница 450: ...Glossary SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 450 ...
Страница 454: ...Index SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 454 ...