Application examples
You can find application examples for PROFINET communication on the Internet:
Controlling the speed of a SINAMICS G110M/G120/G120C/G120D with S7-300/400F via
PROFINET or PROFIBUS, with Safety Integrated (via terminal) and HMI (
support.industry.siemens.com/cs/ww/en/view/60441457
Controlling the speed of a SINAMICS G110M / G120 (Startdrive) with S7-1500 (TO) via
PROFINET or PROFIBUS, with Safety Integrated (via terminal) and HMI (
support.industry.siemens.com/cs/ww/en/view/78788716
4.4.2.3
Installing GSDML
Procedure
1. Save the GSDML to your PC.
– With Internet access:
http://support.automation.siemens.com/WW/view/en/22339653/133100
– Without Internet access:
Insert a memory card into the converter.
Set p0804 = 12.
The converter writes the GSDML as a zipped file (*.zip) into directory /SIEMENS/SINAMICS/
DATA/CFG on the memory card.
2. Unzip the GSDML file on your computer.
3. Import the GSDML into the engineering system of the controller.
You have now installed the GSDML in the engineering system of the controller.
4.4.3
PROFIBUS
4.4.3.1
Integrating the converter in PROFIBUS
Procedure
1. Integrate the converter in the bus system (e.g. line topology) of the control using PROFIBUS
cables and the two PROFIBUS jacks X03 and X04. If your converter forms the end of the line,
only use jack X03 and connect the bus-terminating resistor.
General layout SINAMICS G110M system (Page 29)
The maximum permitted cable length to the previous station and the subsequent one is
100 m at a baud rate of 1 Mbit/s.
2. Externally supply the converter with 24 V DC through X01.
You have now connected the converter to the control system using PROFIBUS DP.
❒
Installation
4.4 Connecting the converter to the fieldbus
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL