Status word 3 (ZSW3)
Bit Meaning
Description
Signal intercon‐
nection in the
converter
0
1 = DC braking active
--
p2051[3] = r0053
1
1 = |n_act | > p1226
Absolute current speed > stationary
state detection
2
1 = |n_act | > p1080
Absolute actual speed > minimum
speed
3
1 = i_act ≧ p2170
Actual current ≥ current threshold
value
4
1 = |n_act | > p2155
Absolute actual speed > speed
threshold value 2
5
1 = |n_act | ≦ p2155
Absolute actual speed < speed
threshold value 2
6
1 = |n_act | ≧ r1119
Speed setpoint reached
7
1 = DC link voltage ≦ p2172
Actual DC link voltage ≦ threshold
value
8
1 = DC link voltage > p2172
Actual DC link voltage > threshold
value
9
1 = ramp-up or ramp-down completed Ramp-function generator is not ac‐
tive.
10 1 = technology controller output at
the lower limit
Technology controller output ≦
p2292
11 1 = technology controller output at
the upper limit
Technology controller out‐
put > p2291
12 Not used
13 Not used
14 Not used
15 Not used
Advanced commissioning
8.6 Drive control via PROFIBUS or PROFINET
Distributed converter for SIMOGEAR geared motors
192
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
Содержание SINAMICS G110M
Страница 2: ......
Страница 426: ...Index Distributed converter for SIMOGEAR geared motors 424 Operating Instructions 10 2020 FW V4 7 SP13 A5E31298649B AL ...