8.17.3
Inhibit direction of rotation
Function description
S
S
[
\
[
\
W
\
\
[
[
In the factory setting of the converter, both motor directions of rotation are enabled.
Set the corresponding parameter to a value = 1 to permanently block directions of rotation.
Example
Table 8-55
Application examples for inhibiting and enabling a direction of rotation
Parameter
Description
p1110[0] = 1
Negative direction of rotation is permanently inhibited.
p1110[0] = 722.3
Digital input 3 = 0: Negative direction of rotation is enabled.
Digital input 3 = 1: Negative direction of rotation is inhibited.
Parameter
Parameter
Description
Factory setting
p1110[C]
BI: Inhibit negative direction
0
p1111[C]
BI: Inhibit positive direction
0
Advanced commissioning
8.17 Setpoint calculation
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
271