7.2.1
Extending the exception list for know-how protection
In the factory setting, the exception list only includes the password for know-how protection.
Before activating know-how protection, you can additionally enter the adjustable parameters in
the exception list, which must still be able to be read and changed by end users – even if know-
how protection has been activated.
You do not need to change the exception list, if, with exception of the password, you do not
require additional adjustable parameters in the exception list.
Absolute know-how protection
If you remove password p7766 from the exception list, it is no longer possible to enter or change
the password for know-how protection.
You must reset the converter to the factory settings in order to be able to gain access to the
converter adjustable parameters. When restoring the factory settings, you lose what you have
configured in the converter, and you must recommission the converter.
Parameter
Parameter
Description
Factory setting
p7763
KHP OEM exception list, number of indices for p7764
1
p7764[0…p7763]
KHP OEM exception list
p7766 is the password for know-how protection
[0] 7766
[1...499] 0
Protecting the converter settings
7.2 Know-how protection
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
151