4.3
Electrical Installation
4.3.1
SINAMICS G110M Electrical data
Power Module specifications - 3AC 380 V (-10%) ... 480 V (+10%)
Table 4-2
Rated Output, Input and Fuses
Product
Frame size
Rated output
HO
Fuse*
Rated out‐
put current
Rated input
current
3NA3…
6SL3517-…
kW
hp
A
A
A
Type
1BE11-3AM0
A
0.37
0.5
1.3
1.3
10
803
1BE12-3AM0
A
0.75
1.0
2.2
2.0
10
803
1BE13-3AM0
A
1.1
1.5
3.1
2.8
10
803
1BE14-3AM0
A
1.5
2.0
4.1
3.6
10
803
1BE16-3AM0
B
2.2
3.0
5.6
5.3
20
807
1BE17-7AM0
B
3.0
4.0
7.3
6.9
20
807
1BE21-0AM0
B
4.0
5.0
8.8
8.0
20
807
*For UL applications use Class J or CC fuses.
Standby current
The converter has a unique standby current characteristic which needs to be taken into account
when calculating the requirements of the line supply.
The standby current is the current that the converter requires when the converter is in the ready-
to-run mode. This means that the converter is powered-up but the motor is not running. The
phenomenon of capacitive reactive current standby occurs in all converters with filter capacitors
on the line side.
In applications where a number of converters are connected to one line supply and where only
a small proportion of the converters will be running at any one time, the standby currents in the
non-running converters must be considered when calculating the size of the conductors and
selecting the correct protective devices on the line supply of the system.
The Control Module (CM) and the communications input and outputs are normally powered by
a Class 2 external 24 V supply, which does not influence the standby current of the converter.
However, the optional 24 V PSU draws it power directly from the DC link of the Power Module
(PM), in this case, the standby current of the converter increases, by an additional current of 15
mA.