Parameter
Parameter
Description
Factory setting
p0010
Drive commissioning parameter filter
1
p9601
SI enable, functions integrated in the drive (processor 1)
0000 0000 bin
p9761
SI password input
0000 hex
p9762
SI password new
0000 hex
p9763
SI password acknowledgment
0000 hex
8.15.2.3
Interconnecting the "STO active" signal
Overview
If you require the feedback signal "STO active" of the converter in your higher-level control
system, then you must appropriately interconnect the signal.
Function description
Procedure
1. Select the button for the feedback signal.
$
The screen form varies depending on the interface selected.
(A)
Control type
2. Select the signal that matches your particular application.
You have interconnected the "STO active" checkback signal.
❒
After STO has been selected, the converter signals "STO active" to the higher-level control.
Example
Parameter
Description
r9773.01
1 signal: STO is active in the drive
Parameter
Parameter
Description
Factory setting
r9773[0…31]
CO/BO: SI status (processor 1 + processor 2)
-
Advanced commissioning
8.15 Safe Torque Off (STO) safety function
Distributed converter for SIMOGEAR geared motors
248
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL