Set the most important parameters to suit your application.
Application:
• [0]: In all applications that do not fall under [3]
• [3]: Applications involving pumps and fans with optimized efficiency. The setting only makes
sense for steady-state operation with slow speed changes.
Motor identification:
• [1]: Recommended setting for "speed control" control type. Measure the motor data at
standstill and with the motor rotating. The converter switches off the motor after the motor
data identification has been completed.
• [2]: Measure the motor data at standstill. The converter switches off the motor after the
motor data identification has been completed.
Recommended setting for the following cases:
– You have selected "Speed control" as control mode, however the motor cannot freely
rotate, e.g. for mechanically limited traversing sections.
– You have set "U/f control" as control mode.
• [3]: Measure the motor data while the motor is rotating. The converter switches off the motor
after the motor data identification has been completed.
Calculating the motor parameters: Select "Complete calculation".
Set the check mark for "RAM data to EEPROM (save data in the drive)" to save your data in the
converter so that it is not lost if the power fails.
Press the "Finish" button.
You have entered all of the data that is necessary for the quick commissioning of the converter.
❒
Commissioning
5.4 Quick commissioning
Distributed converter for SIMOGEAR geared motors
126
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL