RP3 RP2 RP1 RP0 AS-i.P0 = 0 -> alarm messages
AS-i.P0 = 1 -> faults
1
1
1
0
not used
Safety fault (F016xx)
1
1
1
1
Other alarms
Other faults
1)
Only for G115D
2)
Only if F30015 was reparameterized as an alarm
8.7.4
Cyclic and acyclic communication via CTT2
Via CTT2 (Combined Transaction Type 2), both cyclical and acyclical communication is
performed via AS-i. Because only one channel is available (AS-i.DO1 master -> slave or AS-i.DI3
slave -> master), a concurrent cyclical and acyclical data exchange is not possible.
The communication type (cyclical or acyclical) is always coded in the first byte in accordance with
the following table.
Table 8-37
CTT2 commands
Code
(hex)
Explanation/meaning
Followed by
Cyclic communication
Access to analog values via DS140 … DS147. See CP 343−2 / CP
343−2 P AS−Interface master (
support.industry.siemens.com/cs/gb/en/view/1171856
ter 4
4 bytes: PWE1, PWE2
4 bytes: PWE1, PWE2
Acyclic communication - standard
10 hex
Read request: Master -> slave
2 bytes: Index, length
50 hex
Read request OK: Slave -> master
Index, data
90 hex
Read request failed: Slave -> master
1 byte: Standard error code (3 hex)
11 hex
Write request: Master -> slave
Index, length, data
51 hex
Write request OK: Slave -> master
91 hex
Write request failed: Slave -> master
1 byte: Standard error code (3 hex)
Acyclic communication - manufacturer-specific
12 hex
Read request: Master -> slave
Index, length
52 hex
Read request OK: Slave -> master
Data
92 hex
Read request failed: Slave -> master
Fault object
13 hex
Write request: Master -> slave
Index, length, data
53 hex
Write request OK: Slave -> master
93 hex
Write request failed: Slave -> master
Fault object
1D hex
Exchange request: Master -> slave
Index, read length, write length, write
data
5D hex
Exchange request OK: Slave -> master
PKE, index, n-2 data
9D hex
Exchange request faulty: Slave -> master
Fault object
Advanced commissioning
8.7 Control via AS-i
Distributed converter for SIMOGEAR geared motors