Requirement
Application exam‐
ples
Remark
Charac‐
teristic
Parameter
Freely adjusta‐
ble U/f charac‐
teristic
-
-
Adjusta‐
ble char‐
acteristic
p1300 = 3
U/f characteris‐
tic with inde‐
pendent volt‐
age setpoint
-
The interrelationship between the
frequency and voltage is not calcu‐
lated in the converter, but is speci‐
fied by the user.
Inde‐
pendent
voltage
setpoint
p1300 = 19
8.19.1.2
Selecting the U/f characteristic
Parameter
Parameter
Description
Factory setting
r0025
CO: Output voltage, smoothed
- Vrms
r0066
CO: Output frequency
- Hz
r0071
Output voltage, maximum
- Vrms
p0304[M]
Rated motor voltage
0 Vrms
p0310[M]
Rated motor frequency
0 Hz
p1300[D]
Open-loop/closed-loop control operating mode
0
p1333[D]
U/f control FCC starting frequency
0 Hz
p1334[D]
U/f control slip compensation starting frequency
0 Hz
p1335[D]
Slip compensation scaling
0%
p1338[D]
U/f mode resonance damping gain
0