Converter pulse frequency
2 kHz
4 kHz and higher
Pole number of the motor
4-pole
4-pole
Maximum motor speed [rpm]
4980
7200
5.3.4
Minimum and maximum speed
Minimum and maximum speed
• Minimum speed - factory setting 0 [rpm]
The minimum speed is the lowest speed of the motor independent of the speed setpoint. A
minimum speed > 0 is, for example, useful for fans or pumps.
• Maximum speed - factory setting 1500 [rpm]
The converter limits the motor speed to the maximum speed.
Operate the converter with the factory setting
We recommend that you execute quick commissioning. For quick commissioning, you must
adapt the converter to the connected motor by setting the motor data in the converter.
In basic applications with a standard induction motor, you can attempt to operate the drive with
a rated power of < 18.5 kW without carry out an additional commissioning steps. Check whether
the control quality of the drive without commissioning is adequate for the requirements of the
application.
Commissioning
5.3 Prepare commissioning
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
105