3
02.98
1-48
Siemens AG 1998 All Rights reserved 6SN1197–0AA00 02.98 Edition
SIMODRIVE 611 (PJ)
Table 3-15 Auto–transformer for 220V input voltage
2)
I/R module
16/21 kW
I/R module
36/47 kW
I/R module
55/71 kW
I/R module
80/104 kW
I/R module
120/156
kW
PD
type
1)
3–ph.
220/400 V AC
21 kVA
auto–transformer
46.5 kVA
auto–transformer
70.3 kVA
auto–transformer
104 kVA
auto–transformer
155 kVA
auto–transformer
Order No.,
6SN1111–0AA00–
–0BC0
–0CC0
–0DC0
–0EC0
–0FC0
Pv
412 W
644 W
790 W
1100 W
1340 W
Max. connection
cross–section
Prim 16 mm
2
Sec. 16 mm
2
Prim 70 mm
2
Sec. 50 mm
2
Prim 95 mm
2
Sec. 70 mm
2
9 mm diameter drilling
Fuse on the pri-
mary side
63 A gL
160 A gL
224 A gL
300 A gL
500 A gL
Weight
60 kg
120 kg
135 kg
220 kg
300 kg
Terminal assign-
ment
1U1 to 1W1=220 V input, 2U1 to 2W1=400 V output, N=neutral point
Max. dimensions
Drilling template in
mm
Top view
138
264
max.220
max.
370
18
10
Max. height 330
Top view
155
356
max.255
max.
480
22
15
Max. height 430
Top view
182
356
max.300
max.
480
22
15
Max. height 430
Top view
183
410
max.325
max.
530
Max. height 520
12.5
Top view
198
470
max.360
max
.590
Max. height 600
15
The following operating conditions are permitted:
S
Supply voltage 3–ph. 480/440/400 V AC or 3–ph. 220/400 V AC/45...60 Hz
1)
S
Temperature range –25
C...40
C (to 55
C with de–rating)
S
degree of protection IP00
S
humidity rating F according to DIN 40040 for transformers and reactors
The maximum current of transformers/reactors is dependent on the ambient
temperature and the installation altitude. The permissible current/power rating of
the transformers and reactors is:
I
n
(PD) reduced = c
I
n
(PD)
1.1
0.9
0.7
40 50
_
C
mNN
1000 2000
c
a)
b)
a) The ambient temperature above +40
_
C
b) Installation altitude above 1000 m
Reduction factor c
as a function of:
30
Figure 3-11 Reduction factor c
1)
3–ph. 240 V AC at 60 Hz
5% can be used as input voltage.
Note: The secondary voltage increases, and switch S1.1 on the NE modules must be set to ON, refer to p. 1-20.
2) Assignment of the isolating transformers to I/R modules, refer to Catalog NC 60.1 Part 8.
Operating
conditions
of all transformers
and reactors
3.4.3 Assignment of the auto–transformer to the I/R modules
Содержание SIMODRIVE 611A
Страница 2: ......
Страница 6: ......
Страница 7: ...SECTION 0 PRELIMINARY INFORMATION 0 7 ...
Страница 8: ......
Страница 17: ...Section 1 611A Analog Feed Drives 1 17 ...
Страница 18: ...1 18 ...
Страница 24: ...1 24 ...
Страница 39: ...1 39 ...
Страница 70: ...1 70 ...
Страница 119: ...1 119 ...
Страница 120: ......
Страница 123: ......
Страница 131: ......
Страница 158: ...1 158 ...
Страница 159: ...1 159 MOUNTING DIMENSIONS ...
Страница 160: ...1 160 ...
Страница 186: ......
Страница 187: ...GENERAL INFORMATION REGARDING AC SERVO MOTORS AL S ...
Страница 188: ......
Страница 225: ...1FT5 AC SERVO MOTOR DESCRIPTIONS 1FT5 ...
Страница 226: ......
Страница 321: ...FEEDBACK DEVICES FOR 1FT5 GE ...
Страница 322: ......