3
02.98
1-25
Siemens AG 1998 All Rights reserved 6SN1197–0AA00 02.98 Edition
SIMODRIVE 611 (PJ)
Technical data
Technical data, supply infeed modules
Table 3-2 Technical data, supply infeed modules, internal cooling
Des.
P
n
/P
s6
/P
max
for supply in-
feed [kW]
P
n
/P
s6
/P
max
for regenera-
tive feedback.
For UE with
internal pul-
sed resistor
[kW]
Input current
[A]
for 3–ph.
400 V AC,
600 V DC
P
n
/P
s6
/P
max
Max.
cross–sec-
tion
4)
[mm
2
]
Module
width
[mm]
Energy of
the pulsed
resistor
for 1 x bra-
king ope-
ration
Power los-
ses[W]
1)
Pv
tot.
/Pv
ext
/Pv-
int
[kW]
Output cur-
rent [A]
Weight
[kg]
Monitoring module
–
–
16/10
50
–
Monitoring module
70/–/70
–
16/10
5
–
Pulsed resistor
–
0.3/–/25
3)
–
6/4
50
int.: E
max
=
7.5 kWs
Pulsed resistor
/310
310/–/10
2)
(450 V DC)
–
6/4
5
ext.: E
max
=
180 kWs
UE module 5/10 kW
5/6.5/10
0.2/–/10
3)
11.3/14.7/22.6
6/4
50
int.: E
max
=
13.5 kWs
UE module, 5/10 kW
/270
270/–/70
2)
(450 V DC)
9.3/12/18.6
(540 V DC)
6/4
6.5
–
UE module 10/25 kW
10/13/25
0.3/–/25
3)
21.8/28.5/54.5
16/10
100
int.: E
max
=
7.5 kWs
UE module, 10/25 kW
/450
450/–/150
2)
(450 V DC)
18.5/24/46.5
(540 V DC)
16/10
9.5
–
UE module 28/50 kW
28/36/50
0.3/–/25
5)
58.5/75/104.5
50
200
External 1:
E
max
=
7.5 kWs
UE module, 28/50 kW
250/–/250
(450 V DC)
52/67/93
(540 V DC)
50
13.5
External 2:
E
max
=
180 kWs
I/R module 16/21 kW
16/21/35
16/21/35
27/35.5/59
16/10
100
–
I/R module, 16/21 kW
320/–/320
16/21/35
26.5/35/58
16/10
10.5
–
I/R module 36/47 kW
36/47/70
36/47/70
60.5/79/117.5
50
200
–
I/R module, 36/47 kW
585/–/585
36/47/70
60/78/116
50
15.5
–
I/R module 55/71 kW
55/71/91
55/71/91
92.5/119/153
95 or
300
–
I/R module, 55/71 kW
745/–/745
55/71/91
91/118/151
2 x 35
26
–
I/R module, 55/71 kW pipe
55/71/91
55/71/91
92.5/119/153
95 or
300
–
connection
–/630/115
55/71/91
91/118/151
2 x 35
26
–
I/R module, 80/104 kW
pipe connection or radial
80/104/131
80/104/131
134/175/220
95 or
300
–
i e connection or radial
fan
1280/1090/190
80/104/131
133/173/218
2 x 35
26
–
I/R module, 120/156 kW
pipe connection or
120/156/175
120/156/175
202/262/294
150 or
300
–
i e connection or
radial fan
1)
1950/1660/290
120/156/175
200/260/291
2 x 50
28
–
1)
If pipe cooling is not used, only Pv
tot
has to be taken into account.
2)
If the internal pulsed resistor is shutdown, for internal cooling, the only power loss is Pv
int
.
3)
The motor braking energy is converted into heat in the integrted pulsed resistor; a heat barrier may be
required, refer to p. 1-34
4)
The 1st number is for cable lugs, the 2nd number is valid for finely–stranded conductors
without connector sleeve.
5)
It can be used: a) 0.3/25 kW b) 2 x 0.3/25 kW c) 1.5/25 kW d) 2 x 1.5/25 kW
3.2.1 Technical data, supply infeed modules
Содержание SIMODRIVE 611A
Страница 2: ......
Страница 6: ......
Страница 7: ...SECTION 0 PRELIMINARY INFORMATION 0 7 ...
Страница 8: ......
Страница 17: ...Section 1 611A Analog Feed Drives 1 17 ...
Страница 18: ...1 18 ...
Страница 24: ...1 24 ...
Страница 39: ...1 39 ...
Страница 70: ...1 70 ...
Страница 119: ...1 119 ...
Страница 120: ......
Страница 123: ......
Страница 131: ......
Страница 158: ...1 158 ...
Страница 159: ...1 159 MOUNTING DIMENSIONS ...
Страница 160: ...1 160 ...
Страница 186: ......
Страница 187: ...GENERAL INFORMATION REGARDING AC SERVO MOTORS AL S ...
Страница 188: ......
Страница 225: ...1FT5 AC SERVO MOTOR DESCRIPTIONS 1FT5 ...
Страница 226: ......
Страница 321: ...FEEDBACK DEVICES FOR 1FT5 GE ...
Страница 322: ......