Chapter 5 - Fault Tracing
Fault Codes
170 | 180
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2016-06-07
66
1066 Thermistor fault
The thermistor input has detected an increase of
motor temperature.
Check motor cooling and load.
Check thermistor connection
(If thermistor input is not in use it must be
short circuited)
69
1310 Fieldbus
mapping error
Non-existing ID number is used for mapping
values to Fieldbus Process Data Out.
Check parameters in Fieldbus Data Mapping
menu.
1311
Not possible to convert one or more values for
Fieldbus Process Data Out.
The value being mapped may be of an
undefined type. Check parameters in the
Fieldbus Data Mapping menu.
1312
Overflow when mapping and converting values for
Fieldbus Process Data Out (16-bit).
80
1080 Remote Safety 1*
Digital input
Verify the status of the digital input as defined
by Remote Safety 1 (P3.5.1.44).
1180 Remote Safety 2*
Verify the status of the digital input as defined
by Remote Safety 2 (P3.5.1.45).
1280 Remote Safety 3*
Verify the status of the digital input as defined
by Remote Safety 3 (P3.5.1.46).
1380 Remote Safety 4*
Verify the status of the digital input as defined
by Remote Safety 4 (P3.5.1.47).
1480 Remote Safety 5*
Verify the status of the digital input as defined
by Remote Safety 5 (P3.5.1.48).
1580 Remote Safety 6*
Verify the status of the digital input as defined
by Remote Safety 6 (P3.5.1.49).
1680 Remote Safety 7*
Verify the status of the digital input as defined
by Remote Safety 7 (P3.5.1.50).
1780 Remote Safety 8*
Verify the status of the digital input as defined
by Remote Safety 8 (P3.5.1.51).
81
1081 Overload**
Overload Relay has triggered the fault.
Reset the overload relay in the bypass
cabinet.
82
1082 Bypass Not Possible* OPT-B5 relay board is missing. Bypass is not
possible without the relay board.
Verify connection of the OPT-B5 option board
in Slot C, D, or E. Install if required when
power is not applied to the drive.
83
1083 Essential Services*
Essential Services activated through digital input.
Verify the status of the digital input as defined
by Essential Services (P3.5.1.52). Verify the
status of the EssentServEnable (P3.18.5).
84
1084 Run Interlock Proof
The run interlock proof hass failed to be provided
within the time allotted in Run Interlock Proof
(P3.2.13).
Verify proper operation of the proof feedback
source.
101
1101 Process
supervision fault
(PID1)
PID controller: Feedback value outside of
supervision limits (and the delay if set).
105
1105 Process
supervision fault
(PID2)
PID controller: Feedback value outside of
supervision limits (and delay, if set).
* Faults only possible with an Electronic Bypass Option.
** Faults only possible with a Bypass Option.